TO-6 surge protective device SPD 100KA

TO-6 surge protective device SPD 100KA
Product Detailed
TO-6 surge protective device SPD 100KA Uc:~385VAC In(8/20):100KA Imax(8/20):150KA Up:less than or equal to 3.0KA

TO-6 surge protective device SPD 100KA:

Product Description

TO-B series surge protective device(in short:SPD,alias:surge protector,surge arrester)is suitable for TN-S,TN-C-S,TT,IT etc.power supply system of AC 50/60Hz.≤380V,and used at the equipotential connection,which protects the 

electric network not shocked by the thunder and lightning,it's designed according to GB18802.1,IEC61643-1,it adopts 35mm standard rail,there is a failure release mounted on the module of surge protective device,

When the SPD fails in breakdown for over-heat and over-current,

the failure release will help electric device separate from the power system and give the indication signal,green means 

normal,red means abnormal,Kevin wiring mode,remote signaling output interface.it's also could be replaced for the 

module when has operating voltage.

Application Scope and Installation Position

TO-B-150,TO-B-120,TO-B-100 series surge protective devices are suitable for B grade lightning-proof,

used at the quipotential connection of LPZOA or LPZOB and LPZ1 zone,which protects the electrle network not 

shocked by the thunder.TO6-80,TO6-60 series surge protective devices are usually 

installed in low voltage main distribution box connected to the incoming end of the buildings.

Notice:When you order our goods,please write the model and quantity carefully.For example:TO-B-150/4-385,8PCS

Model

TO-B

200

TO-B

150

TO-B

120

TO-B

100

TO-B

80

TO6

60

Technical Parameters

      

Rated Operating Voltage Un(V~)

220V/380V

Maximum Continuous Operating Voltage Uc(V~)

385/420V

Voltage Protection Level Up(V~)KV

≤4.0

≤3.2

≤3.0

≤2.8

≤2.4

≤2.2

Maximum Discharge Current Imax(8/20us)KA

150

150

120

100

80

60

Nominal Discharge Current In(8/20us)KA

200

100

80

60

40

30

Response Times

<2.5

The Cross Section of L/N Line

25,35

16,25

16,25

16,25

16,25

The Cross Section of PE line (mm²)

35

25,35

25,35

25,35

16,25

Fuse or Switch(A)

63A,125A

63A

63A

63A

63A,32A

The Line Section of Communication and Alarm

≤1.5

Operating Environment°C

-40°C~+85°C

Relative Humidity(25°C)

≤95%

Installation

Standard Rail 35mm

Material of Outer Covering

Fiber glass reinforced plastic